DISCUSSION OF THERMAL ACTIVATION ON HEAT COLLECTION PLATE OF SPRINKLER HEADS

ABSTRACT
Heat collection plates (HCP) are installed above sprinkler heads in some tall halls in the Asia-Oceania region to give faster thermal actuation. In this study, experiments were thus conducted in a fire chamber to determine thermal activation times of sprinkler heads with and without HCP. Three HCP with different diameters were selected and tested with pendent fast response liquid-in-bulb sprinkler heads. A total of 48 sprinklers heads were studied under different conditions of height and pool fire size. The HCP was found to reduce sprinkler activation time in a fire chamber test by up to 61%. Thermal activation time of sprinkler heads was also investigated by the common plunge test in a wind tunnel. Results indicate that activation was delayed by 5%, 18%, and 221% on average by the three HCP. An HCP of pie plate shape with small diameter would alter the physical scenario of heating up the heat sensing element of sprinkler heads assumed in the plunge test. Therefore, the effect of HCP cannot be appropriately assessed in a wind tunnel.
KEYWORDS
PAPER SUBMITTED: 2023-04-02
PAPER REVISED: 2023-06-06
PAPER ACCEPTED: 2023-06-09
PUBLISHED ONLINE: 2023-09-02
DOI REFERENCE: https://doi.org/10.2298/TSCI230402176S
CITATION EXPORT: view in browser or download as text file
THERMAL SCIENCE YEAR 2024, VOLUME 28, ISSUE Issue 2, PAGES [903 - 911]
REFERENCES
  1. Ivanov, M. L., Chow, W. K., Fire Safety in Modern Indoor and Built Environment, Indoor Built Environ, 32 (2023) 1, pp. 3-8
  2. ***, Code of Practice for Fire Safety in Buildings 2011 (June 2023 version), Buildings Department, Hong Kong, China, 2011
  3. ***, BS EN 12845:2015+A1:2019 Fixed Firefighting Systems - Automatic Sprinkler Systems - Design, Installation and Maintenance. British Standards Institution, UK, 2019
  4. ***, Fire Services Department, Codes of Practice for Minimum Fire Service Installations and Equipment and Inspection, Testing and Maintenance of Installations and Equipment. Hong Kong, 2022
  5. Chow, W. K., Performance of Sprinkler in Atria, J. Fire Sci., 14 (1996) 6, pp. 466-488
  6. Yang, K. H., Yeh, T. C., Design Analysis and Experimental Investigation of the Smoke Management System Performances of an HSR Station, Int. J. Architectural Science, 6 (2005) 3, pp. 106-113
  7. Chow, W. K., et al., Numerical Studies on Atrium Smoke Movement and Control with Validation by Field Tests, Build. Environ., 44 (2009) 6, pp. 1150-1155
  8. Chow, W. K., On the Evaporation of Sprinkler Water Spray, Fire Technol., 25 (1989), Nov., pp. 364-373
  9. Arnott, M., et al., Application of a Judgement Method to Regulatory Impact Assessments for Sprin-kler Protection to English High-Rise Residential Buildings, Fire Mater., 45 (2021) 6, pp. 811-822
  10. Lin, S. L., et al., Effect of Heat Collector Plate on Thermal Sensitivity of Sprinkler Heads in Large Ter-minal Halls, J. Build. Eng., 25 (2019) 100787
  11. ***, NRC Information Notice 2002-24: Potential Problems with Heat Collectors on Fire Protection Sprin-klers, USA, 2002
  12. Tsai, K. C., et al., Validating the Function of Absorber Plates for Auto-Sprinkler System Activation, Pro-ceedings, 10th Asia-Oceania Symposium on Fire Science and Technology 2015, Springer Science+Busi-ness Media, Singapore, 2017, pp. 851-857
  13. Chow, W. K., Cheng, A. C. K., Preliminary Studies on Thermal Sensitivity of Fusible Links with a Wind Tunnel, Int. J. Engineering Performance-Based Fire Codes, 9 (2007), 1, pp. 1-6
  14. ***, The Standard for Installation of Fire Safety Equipment based on Use and Occupancy (in Chinese), Taiwanese Regulation, Taipei, Taiwan, 2011
  15. Heskestad, G., Smith, H. F., Plunge Test for Determination of Sprinkler Sensitivity, FMRC 3A1E2.RR, Factory Mutual Research Corporation, Norwood, Mass., USA, 1980
  16. Theobald, C. R., Thermal Response of Sprinklers Part I. FRS Heated Wind Tunnel, Fire Saf. J., 12 (1987) 1, pp. 51-63
  17. Melinek, S. J., Thermal Response of Sprinklers - A Theoretical Approach, Fire Saf. J., 3 (1988) 2/3, pp. 169-180
  18. Chow, W. K., Ho, P. L., Thermal Response of Sprinkler Head, Build. Serv. Eng. Res. Technol., 11 (1990) 2, pp. 37-47
  19. ***, US 5497834A. Sprinkler Head with Plate for Absorbing and Indicating Shocks Thereto, United States Patent Number 5497834, 1996
  20. Chow, W. K., Wu, H. H., Thermal Sensitivity of Fusible Links for Hotel Projects, J. Applied Fire Science, 14 (2009-2010) 2, pp. 123-132
  21. Liu, J. S., et al., Analysis of the Effectiveness of Heat-Collection Plate, Procedia Eng., 135 (2016), pp. 160-169
  22. Liu, H., et al., Critical Assessment on Operating Water Droplet Sizes for Fire Sprinkler and Water Mist Systems, J. Build. Eng., 28 (2020) 100999
  23. ***, National Fire Protection Association, NFPA 13 Standard for the Installation of Sprinkler Systems, 2019 Edition, USA
  24. ***, British Standards Institution, BS EN 12845:2015+A1:2019 Fixed Firefighting Systems - Automatic Sprinkler Systems - Design, Installation and Maintenance, UK, 2019
  25. Novozhilov, V., Application of Heat-Balance Integral Method to Conjugate Thermal Explosion, Thermal Science, 13 (2009), 2, pp. 73-80
  26. Jia, Z. W., et al., Propagation Law of Flame in a Pipeline Produced in Gas Explosion Numerical Analysis and Experimental Verification, Thermal Science, 25 (2021), 3B, pp. 2199-2204
  27. Hung, H. Y., et al., Observation on a Fire Whirl in a Vertical Shaft Using High-Speed Camera and Asso-ciated Correlation Derived, Thermal Science, 25 (2021), 2A, pp. 1001-1012
  28. Zatao-Samedi, O., et al., Effect of Ratio between Incoming Cool Air and Outgoing Hot Gases on Behav-iour of Compartment Fire, Thermal Science, 25 (2021), 1A, pp. 221-228
  29. Xi, Y. H., et al., Numerical Simulation on Temperature in Wood Crib Fires, Thermal Science, 25 (2021), 4A, pp. 2621-2636
  30. Ho, H-H., et al., Numerical Studies on an Accidental Flash Fire at a Water Fun Park by FLACS Software, Thermal Science, 26 (2022), 2C, pp. 1721-1732
  31. Wang, Y., et al., Wind Action on Whirling Flame Characteristics, Thermal Science, 27 (2023), 2A, pp. 1301-1311
  32. ***, ISO 6182-1:2021, Fire protection - Automatic sprinkler systems - Part 1: Requirements and test methods for sprinklers. International Organization for Standardization, Geneva, Switzerland
  33. ***, ISO 6182-7:2020, Fire protection - Automatic sprinkler systems - Part 7: Requirements and test methods for early suppression fast response (ESFR) sprinklers. International Organization for Standardi-zation, Geneva, Switzerland
  34. ***, ISO 6182-10:2014, Fire protection - Automatic sprinkler systems - Part 10: Requirements and test methods for domestic sprinklers. International Organization for Standardization, Geneva, Switzerland
  35. ***, ISO 6182-13:2017, Fire protection - Automatic sprinkler systems - Part 13: Requirements and test methods for extended-coverage sprinklers. International Organization for Standardization, Geneva, Swit-zerland
  36. ***, Legislative Council Panel on Manpower Safety in the Use of Tower Cranes on Construction Sites, LC Paper No. CB(2)2480/07-08(01), Labour and Welfare Bureau, Labour Department, Hong Kong, China, 2008
  37. ***, Hong Kong Housing Authority, Safety & Health Circular No. 10/2009 Alert on Safe Handling of Tower-Crane Lifting Operations, 2009
  38. ***, The Standard, One Hospitalized as San Po Kong Fire Burns for More Than Four Hours, 2023 www.thestandard.com.hk/breaking-news/section/4/199666/
  39. Chow, W. K., On the Fire Safety Requirements for Existing Old Buildings, Int. J. Engineering Perfor-mance-Based Fire Codes, 9 (2007) 1, pp. 31-37
  40. Lo, C., et al., Collapsed Tower Crane that Killed 3 Workers in Hong Kong Suspected To Have Had ‘Ob-vious Faults' at its Base, South China Morning Post, Hong Kong, China, 2022 www.scmp.com/news/hong-kong/society/article/3191621/tower-crane-collapses-and-knocks-con-tainer-8-workers-hong
  41. Kong, H., Lo, C., Mirror Concert Accident: Fallen Screen at Hong Kong Show Weighed Twice Value Reported to Authorities, South China Morning Post, Hong Kong, China, 2022 www.scmp.com/news/hong-kong/law-and-crime/article/3190162/weight-screen-fell-mirror-con-cert-and-injured-two
  42. ***, Bosses Could Be Fined HK$10m, Jailed Two Years for Safety Breaches as Latest Bill Passes, The Standard, 2023 www.thestandard.com.hk/breaking-news/section/4/202780/
  43. ***, Beijing District Official Apologises After Hospital Fire Kills 29 People, South China Morning Post, Hong Kong, China, Injures Dozens, 2023, www.scmp.com/news/china/politics/arti-cle/3217559/death-toll-beijing-hospital-fire-rises-29-dozens-injured
  44. ***, Safety Checks at Skyscraper After Hong Kong Firefighters Battle Blaze for 9 Hours in Major Shop-ping District Tsim Sha Tsui, 2023, South China Morning Post, Hong Kong, China www.scmp.com/news/hong-kong/law-and-crime/article/3212152/two-taken-hospital-after-major-fire-hits-skyscraper-under-construction-hong-kongs-tsim-sha-tsui

© 2024 Society of Thermal Engineers of Serbia. Published by the Vinča Institute of Nuclear Sciences, National Institute of the Republic of Serbia, Belgrade, Serbia. This article is an open access article distributed under the terms and conditions of the Creative Commons Attribution-NonCommercial-NoDerivs 4.0 International licence