ENERGY-SAVING AND EMISSION REDUCTION SYSTEM OF DATA CENTER HEAT PIPE BASED ON LATENT HEAT OF WATER EVAPORATION

ABSTRACT
To address the current problem of high energy consumption in data centers, this paper proposes a data center heat pipe air-conditioning system based on the latent heat of water evaporation, which uses the latent heat of water evaporation for cooling by creating a low pressure environment to evaporate large amounts of water. In order to verify the effect of the system, a heat pipe test bench based on the latent heat of water evaporation was designed and built. Compared with the traditional heat pipe in the data center for heat dissipation, the performance and economy of the water evaporation latent heat pipe system designed in this paper are analyzed experimentally. A multi-physics coupled model of water evaporation latent heat pipe air-conditioning based on COMSOL Multiphysics was established to simulate and study the temperature field and velocity field distribution of water evaporation latent heat pipe air-conditioning system in data centers. The research shows that: - Under the designed test conditions, compared with the traditional heat pipe system, the water evaporation latent heat pipe air conditioner can conduct 2540 kJ more heat in one day in an outdoor environment of 24°C. - At an ambient temperature of 35°C and an indoor temperature of 25.8 °C, the cooling capacity of the heat pipe in the data center water evaporation latent heat pipe air-conditioning system is twice the cooling capacity of the air conditioner, and the heat pipe can work efficiently regardless of the outdoor ambient temperature. - The energy-saving effect of the latent heat pipe of water evaporation in the data center has a significant effect on air conditioners with an energy efficiency rating (EER) lower than 2.5-4.4. It can improve the energy efficiency of level 5 with an EER of 2.5 to level 2 with an EER of 3.22, greatly reducing the power consumption of the data center air-conditioning system. When the EER of the air conditioner exceeds 4.4, the coefficient of performance of the data center water evaporation latent heat pipe air-conditioning system will be lower than that of the air conditioner itself.
KEYWORDS
PAPER SUBMITTED: 2022-05-18
PAPER REVISED: 2022-07-20
PAPER ACCEPTED: 2022-08-19
PUBLISHED ONLINE: 2022-10-29
DOI REFERENCE: https://doi.org/10.2298/TSCI2205475Z
CITATION EXPORT: view in browser or download as text file
THERMAL SCIENCE YEAR 2022, VOLUME 26, ISSUE Issue 5, PAGES [4475 - 4487]
REFERENCES
  1. Sun, W., Qian, R., Heat Pipe Air Conditioner Using Natural Energy, Proceedings, China Communica-tion Energy Conference Paper Collection, Xi'an, China, 2017, pp. 170-171
  2. Jing, H., et al., Research on Performance of Natural Cooling Energy Heat Exchanger Based on Flat Plate Micro Heat Pipe Array, Data RoomBuilding Science, 36 (2020), 04, pp. 114-122
  3. Wang, F., et al., Design and Analysis of Heat Pipe Type Server Room Air-conditioning System, Refrig-eration and Air-Conditioning, 18 (2018), 05, pp. 4-8
  4. He, Z., et al., Application of Heat Pipe Air-conditioning System in High Heat Density Data Room, Refrigeration, 40 (2021), 03, pp. 54-57
  5. Liu, H., et al., Analysis of Operating Characteristics of Separate Heat Pipe Radiator for Data Room, Building Energy Efficiency, 45 (2017), 10, pp. 6-11
  6. Zhang, Y., et al., Discussions of Cold Plate Liquid Cooling Technology and Its Applications in Data Center Thermal Management, Frontiers in Energy Research, 10 (2022), June, 954718
  7. Gan, T. K., et al., Thermal Analysis of Water-Filled Micro Heat Pipes of Natural-Convection Water Heat Sink, International Journal of Heat and Mass Transfer, 19 (2022), July, 122741
  8. Borodinecs, A., et al., Feasibility of Reducing Electricity Consumption of Air-conditioning Equipment by Condenser Direct Evaporative Cooling Technology, Example of Case Study in Dubai, Atmosphere, 12 (2021), 9, 1205
  9. Yang, H., et al., Research Development of Indirect Evaporative Cooling Technology: An Updated Re-view, Renewable and Sustainable Energy Reviews, 145 (2021), July, 111082
  10. Pacak, A., Worek, W., Review of Dew Point Evaporative Cooling Technology for Air-conditioning Applications, Applied Sciences, 11 (2021), 3, 934
  11. Tushar, S.. et al.,Experimental Performance and Parametric Analysis of Heat Pipe Heat Exchanger for Air-Conditioning Application Integrated with Evaporative Cooling, Heat and Mass Transfer, 53 (2017), 11, pp. 3287-3293
  12. Dong, D., et al., Theoretical and Experimental Validation Study on Automotive Air-Conditioning Based on Heat Pipe and LNG Cold Energy for LNG-Fueled Heavy Vehicles, Heat and Mass Transfer, 53 (2017), 11, pp. 2551-2558
  13. Tan, R., Zhang, Z., Heat Pipe Structure on Heat Transfer and Energy Saving Performance of the Wall Implanted with Heat Pipes During the Heating Season, Applied Thermal Engineering, 102 (2016), June, pp. 633-640
  14. Li, L., et al., A State-of-the-Art Review on the Application of Heat Pipe System in Data Centers, Ap-plied Thermal Engineering, 199 (2021), Nov., 117618
  15. ***, Environment; New Environment Findings from Changchun Institute of Technology Published (An experimental study on heat transfer performance of a pulsating heat pipe radiator for CPU heat dissipa-tion). Ecology, Environment & Conservation, 2020
  16. Zhang, H., et al., A Review on Thermosyphon and Its Integrated System with Vapor Compression for Free Cooling of Data Centers, Renewable and Sustainable Energy Reviews, 81 (2018), Part 1, pp. 789-798
  17. Salih, E. H., et al., Experimental Demonstration and Flow Network Model Verification of Induced CRAH Bypass for Cooling Optimization of Enclosed-Aisle Data Centers, IEEE Transactions on Com-ponents, Packaging and Manufacturing Technology, 7 (2017), 11, pp 1795-1803
  18. Ikeda, T., et al., Using Latent Heat of Water Evaporation to Cool the Culture Medium for High-Bench Strawberry Culture, Acta Horticulturae, 708 (2006), 708, pp. 393-396
  19. Ali, M. A., et al., A Hybrid Domed Roof and Evaporative Cooling System: Thermal Comfort and Building Energy Evaluation, Sustainable Cities and Society, 80 (2022), May, 103756
  20. Ramy, M. H., et al., Indirect Evaporative Cooling for Buildings: A Comprehensive Patents Review., Journal of Building Engineering, 50 (2022), June, 104158

© 2024 Society of Thermal Engineers of Serbia. Published by the Vinča Institute of Nuclear Sciences, National Institute of the Republic of Serbia, Belgrade, Serbia. This article is an open access article distributed under the terms and conditions of the Creative Commons Attribution-NonCommercial-NoDerivs 4.0 International licence