THE ENERGY AND EXERGY ANALYSIS ON THE PERFORMANCE OF COUNTER-FLOW HEAT AND MASS EXCHANGER FOR M-CYCLE INDIRECT EVAPORATIVE COOLING

ABSTRACT
The dew point Indirect Evaporative Cooling (IEC) achieved through Maisotsenko cycle (M-Cycle) is a complicated thermodynamic process. For further understanding of the heat and mass transfer occurred in a dew point indirect evaporative air cooler with M-Cycle counter-flow configuration, the paper presents a novel mathematical model that combined the law of energy conservation and the principle of the thermodynamic theory. The model was used to carry out the parametric study of the dew point air cooler under various inlet air temperature and relative humidity. Through the combined analysis of energy and exergy of the target IEC system, it is found that both the inlet air temperature and relative humidity have an important effect on the thermal performance and thermodynamic performance of the heat and mass exchanger. The high temperature environment helps to get better thermal performance and thermodynamic performance. It has been showed in this paper that the best thermal performance does not correspond to the best thermodynamic performance. Thus, the energy and exergy analysis should be implemented simultaneously for the optimization of the process to get the best thermal performance at permissible level of thermodynamic cost.
KEYWORDS
PAPER SUBMITTED: 2017-12-21
PAPER REVISED: 2018-05-07
PAPER ACCEPTED: 2018-05-13
PUBLISHED ONLINE: 2018-05-20
DOI REFERENCE: https://doi.org/10.2298/TSCI171221153W
CITATION EXPORT: view in browser or download as text file
THERMAL SCIENCE YEAR 2019, VOLUME 23, ISSUE Issue 2, PAGES [613 - 623]
REFERENCES
  1. Gillan, L., Maisotsenko cycle for cooling processes, Int. J. Energy Clean Environ, 9(2008), pp. 47-64.
  2. Zhao, X. D., et al., Numerical study of a novel counter-flow heat and mass exchanger for dew point evaporative cooling, Applied Thermal Engineering, 28(2008), pp. 1942-1951.
  3. Riangvilaikul, B., Kumar, S., Numerical study of a novel dew point evaporative cooling system, Energy and Buildings, 42(2010), pp. 2241-2250.
  4. Zhan, C. H. , et al., Comparative study of the performance of the M-cycle counter-flow and cross-flow heat exchangers for indirect evaporative cooling - Paving the path toward sustainable cooling of buildings, Energy, 36(2011) , pp. 6790-6805.
  5. Xu P., et al., Numerical investigation of the energy performance of a guideless irregular heat and mass exchanger with corrugated heat transfer surface for dew point cooling. Energy, 109(2016), pp. 803-817.
  6. Lin J., et al., Study on dew point evaporative cooling system with counter-flow configuration, Energy Conversion and Management, 109(2016), pp. 153-165.
  7. Riangvilaikul B., Kumar S., An experimental study of a novel dew point evaporative cooling system, Energy and Buildings, 42(2010), pp. 637-644.
  8. Bruno, F., On-site experimental testing of a novel dew point evaporative cooler, Energy and Buildings, 43(2011), pp. 3475-3483.
  9. Hasan, A., Indirect evaporative cooling of air to a sub-wet bulb temperature, Applied Thermal Engineering, 30(2010), pp. 2460-2468.
  10. Hasan, A., Going below the wet-bulb temperature by indirect evaporative cooling: Analysis using a modified ε-NTU method, Applied Thermal Engineering, 89(2012), pp. 237-245.
  11. Cui, X., et al., Fundamental formulation of a modified LMTD method to study indirect evaporative heat exchangers, Energy Conversion and Management, 88(2014), pp. 372-381.
  12. Bejan, A., Advanced engineering thermodynamics, Cambridge University Press, New York, USA, 1997.
  13. Lu, S. S., et al., Exergetic analysis of cooling systems with ozonation water treatment, Energy Conversion and Management, 39(1998), pp. 1407-1422.
  14. Ren, C. Q., et al., Principles of exergy analysis in HVAC and evaluation of evaporative cooling schemes, Building and Environment, 37(2002), pp. 1045-1055.
  15. Muangnoi, T., et al., An exergy analysis on the performance of a counterflow wet cooling tower, Applied Thermal Engineering, 27(2007), pp. 910-917.
  16. Muangnoi, T., et al., Effects of inlet relative humidity and inlet temperature on the performance of counterflow wet cooling tower based on exergy analysis, Energy Conversion and Management, 49(2008), pp. 2795-2800.
  17. Qureshi, B. A., Zubair W. S., An exergy analysis on the performance of a counterflow wet cooling tower, Applied Thermal Engineering, 27(2007), pp. 910-917.
  18. Santos, J. C., et al., Energy and exergy analysis applied to the evaporative cooling process in air washers, International Journal of refrigeration, 36(2013), pp. 1154-1161.
  19. Taufiq, B. N., et al., Exergy analysis of evaporative cooling for reducing energy use in a Malaysian building, Desalination, 9(2007), pp. 238-243.
  20. Saravanan, M. N., et al., Energy and exergy analysis of counter flow wet cooling towers, Thermal Science, 12(2008), pp. 69-78.
  21. Wang, L, Li N. P., Exergy transfer and parametric study of counter flow wet cooling towers, Applied Thermal Engineering, 31(2011), pp. 954-960.
  22. Moien, F. F, et al., Exergy analysis of evaporative cooling to select the optimum system in diverse climates, Energy, 40(2012), pp. 250-257.
  23. Caliskan, H., et al., Exergetic and sustainability performance comparison of novel and conventional air cooling systems for building applications, Energy and Buildings, 43(2011), pp. 1461-1472.
  24. Zhang, L, et al., Exergy analysis of parameter unmatched characteristic in coupled heat and mass transfer between humid air and water, International Journal of Heat and Mass Transfer, 84(2015), pp. 327-338.
  25. Zhao, X. D., et al., Comparative study of heat and mass exchanging materials for indirect evaporative cooling systems, Building and Environment, 43(2008), pp. 1902-1911.
  26. Baehr, H. D., Stephan, K., Heat and mass transfer, Springer, New York, USA, 2006.
  27. Kays, W. M., Whitelaw J. H., Convective heat and mass transfer, Cambridge University Press, New York, USA, 2011.
  28. Bergman, T. L., et al., Fundamentals of heat and mass transfer. John Wiley & Sons, New York, USA, 2011.
  29. Jason, W., Eric K., A desiccant-enhanced evaporative air conditioner: Numerical model and experiments, Energy Conversion and Management, 65(2013), pp. 208-220.

© 2024 Society of Thermal Engineers of Serbia. Published by the Vinča Institute of Nuclear Sciences, National Institute of the Republic of Serbia, Belgrade, Serbia. This article is an open access article distributed under the terms and conditions of the Creative Commons Attribution-NonCommercial-NoDerivs 4.0 International licence