ABSTRACT
In many heating, ventilation and air-conditioning (HVAC) applications, heat recovery devices are installed, aiming at reducing energy consumption. Especially in buildings requiring a high percentage of outside air for ventilation, there is a high potential for heat recovery from exhaust air. Climatic conditions are an important parameter which affects the recovered heat and the payback period of the heat recovery device. In this paper, a 250 person auditorium is used as a model to estimate the applicability of an air-to-air fixed-plate heat exchanger installed in the air handling unit of the HVAC system. The application is considered for four cities, representative of climatic zones A, B, C, D of Greece, which also represent typical Mediterranean climate conditions. Zone A, Crete and Southern Greece, is similar to Nicosia (Cyprus) and Palermo (Sicily), Zone B, with Athens, corresponds to Rome (Italy) and coastal Spain, Zone C with Thessaloniki is similar to the Toulon (France) and Split (Croatia) and Zone D, with its continental climate is more like Milan (Italy) and Lyon (France). An energy analysis with the modified bin method energy calculation was performed to calculate (a) the heating and cooling energy that can be recovered, (b) the reduction in HVAC equipment, and (c) the expected payback period. For the specific climatic conditions examined, it was proven that: heating energy consumption decreased by 31 to 40%, depending on occupancy, while electric energy consumption didn’t change notably; the payback period does not exceed 24 months, depending on climate zone and occupancy.
KEYWORDS
PAPER SUBMITTED: 2017-09-16
PAPER REVISED: 2017-11-12
PAPER ACCEPTED: 2017-11-21
PUBLISHED ONLINE: 2018-02-18
THERMAL SCIENCE YEAR
2018, VOLUME
22, ISSUE
Supplement 3, PAGES [S933 - S943]
- ***, ASHRAE, Chap. 44 - Air-to-Air Energy Recovery, in: 2004 ASHRAE Handbook - HVAC Systems and Equipment, American Society of Heating, Refrigerating, and Air-Conditioning Engineers, Inc., Atlanta Geo., USA, 2008, pp. 25.1-25.25
- Besant, R., Simonson, C., Air-to-Air Exchangers, ASHRAE Journal, 45 (2003), 4, pp. 42-50
- Mardiana-Idayu, A., Riffat, S.B., Review on Heat Recovery Technologies for Building Applications, Renewable and Sustainable Energy Reviews, 16 (2012), pp. 1241-1255
- Cuce, P.M., Riffat, S.B., A Comprehensive Review of Heat Recovery Systems for Building Applications, Renewable and Sustainable Energy Reviews, 47 (2015), pp. 665-682
- Fehrm, M., et al., Exhaust Air Heat Recovery in Buildings, International Journal of Refrigeration, 25 (2002), pp. 439-449
- Besant, R.W., Simonson, C.J., Air-to-Air Energy Recovery, ASHRAE Journal, 42 (2000), 4, pp. 31-38
- Lazzarin, R.M., Gasparella A., Technical and Economical Analysis of Heat Recovery in Building Ventilation Systems, Applied Thermal Engineering, 18 (1998), 1-2, pp. 47-67
- Zhong, K., Kang Y., Applicability of Air-to-Air Heat Recovery Ventilators in China, Applied Thermal Engineering, 29 (2009), pp. 830-840
- Zhou, Y.P., et al., Performance of energy recovery ventilator with various weathers and temperature set-points, Energy and Buildings, 39 (2007), 12, pp. 1202-1210
- Kang, Y., et al., Temperature Ranges of the Application of Air-to-Air Heat Recovery Ventilator in Supermarkets in Winter, China, Energy and Buildings, 42 (2010), 12, pp. 2289-2295
- Liu, J., et al., Efficiency of Energy Recovery Ventilator with Various Weathers and Its Energy Saving Performance in a Residential Apartment, Energy and Buildings 42 (2010), 1, pp. 43-49
- Knebel, D., Simplified energy analysis using the modified bin method, American Society of Heating Refrigerating and Air-Conditioning Engineers, Inc., Atlanta Geo., USA, 1983
- ***, ASHRAE, Chap. 25 - Heating Load, in: 1985 ASHRAE Handbook - Fundamentals, American Society of Heating, Refrigerating, and Air-Conditioning Engineers, Inc., Heating load, Atlanta Geo., USA, 1985, pp. 25.1-25.10
- ***, ASHRAE, Chap. 25 - Air-Conditioning Cooling Load, in: 1985 ASHRAE Handbook - Fundamentals, American Society of Heating, Refrigerating, and Air-Conditioning Engineers, Inc., Air conditioning Load, Atlanta Geo., USA, 1985, pp. 26.1-26.42
- ***, Technical Directive of the Technical Chamber of Greece 2425/86, Building installations: Data for calculation air-conditioning loads in building spaces (in Greek), Technical Chamber of Greece, Athens, Greece, 1987
- ***, Technical Directive of the Technical Chamber of Greece 20701-3/2010, Climatic data of Greek regions (in Greek), Technical Chamber of Greece, Athens, Greece, 2012
- ***, Official Government Gazette EK407/B/9.4.2010, Regulation on Energy Performance in the Building Sector - KENAK (in Greek), Ministry of Environment Energy and Climate Change, Greece, 2010
- Karadaglis, C., Felekis P., Estimation of bin temperature data in 38 Greek cities (in Greek), Diploma thesis, Department of Mechanical Engineering, Aristotle University Thessaloniki, Thessaloniki, 2006
- Papakostas, K., et al., Bin Weather Data for 38 Greek Cities, Applied Energy, 85 (2008), pp. 1015-1025
- Zagana Papavasileiou, P., Updating of temperature database of Athens and Thessaloniki for energy studies: Period 1983-2012 (in Greek), Diploma thesis, Department of Mechanical Engineering, Aristotle University Thessaloniki, Thessaloniki, 2013
- Tafelmeier, S., et al., Annual Performance of Sensible and Total Heat Recovery in Ventilation Systems: Humidity Control Constraints for European Climates, Buildings, 7 (2017), 28 doi:10.3390/buildings7020028