THERMAL SCIENCE

International Scientific Journal

External Links

HEAT PIPE HEAT EXCHANGER AND ITS POTENTIAL TO ENERGY RECOVERY IN THE TROPICS

ABSTRACT
The heat recovery by the heat pipe heat exchangers was studied in the tropics. Heat pipe heat exchangers with two, four, six, and eight numbers of rows were examined for this purpose. The coil face velocity was set at 2 m/s and the temperature of return air was kept at 24°C in this study. The performance of the heat pipe heat exchangers was recorded during the one week of operation (168 hours) to examine the performance data. Then, the collected data from the one week of operation were used to estimate the amount of energy recovered by the heat pipe heat exchangers annually. The effect of the inside design temperature and the coil face velocity on the energy recovery for a typical heat pipe heat exchanger was also investigated. In addition, heat pipe heat exchangers were simulated based on the effectiveness-NTU method, and their theoretical values for the thermal performance were compared with the experimental results.
KEYWORDS
PAPER SUBMITTED: 2010-08-18
PAPER REVISED: 2014-08-14
PAPER ACCEPTED: 2015-03-08
PUBLISHED ONLINE: 2015-03-08
DOI REFERENCE: https://doi.org/10.2298/TSCI100818020Y
CITATION EXPORT: view in browser or download as text file
THERMAL SCIENCE YEAR 2015, VOLUME 19, ISSUE Issue 5, PAGES [1685 - 1697]
REFERENCES
  1. Dunn, P. D., Reay, D. A., Heat Pipes, Pergamon Press, Oxford, 1994
  2. YAU, Y.H., Ahmadzadehtalatapeh, M., Predicting yearly energy recovery and dehumidification enhancement with a heat pipe heat exchanger using typical meteorological year data in the tropics, Journal of Mechanical Science and Technology (JMST), 25(4)(2011), pp. 847-853
  3. Yau, Y. H., Tucker, A. S., The Performance Study of a Wet Six-Row Heat Pipe Heat Exchanger Operation in Tropical Buildings, International Journal of Energy Research, 27 (2003), pp. 187- 202
  4. Khattar, M. K., Heat Pipes for Terrestrial Applications in Dehumidification Systems, Proceedings-Space Congress, Twenty-fifth Space Congress, Proceedings, Heritage, Dedication, Vision, Canaveral Council of Technical Societies, Cape Canaveral, FL, USA, 1988
  5. YAU, Y.H., Ahmadzadehtalatapeh, M., A Review of Horizontal Heat Pipe Heat Exchangers and their Applications in the Tropics, Applied Thermal Engineering, 30(2-3)(2009), pp. 77-84
  6. Mathur, G. D., Using Heat Pipe Heat Exchangers for Reducing High Energy Costs of Treating Ventilation Air, Proceedings, The Intersociety Energy Conversion Engineering Conference, USA, 1996, Vol. 2, pp. 1447-1452
  7. Mostafa, A. A, Mousa, M. M, Heat Pipe Heat Exchanger for Heat Recovery in Air Conditioning, Applied Thermal Engineering, 27 (2007), pp. 795-801
  8. Abtahi, H., Jayanth, M., Khattar, M. K., Theoretical Analysis of the Performance Characteristics of Dehumidification Heat Pipe Heat Exchangers in Air-Conditioning Systems, Proceedings, The 1988 National Heat Transfer Conference, Houston, TX, USA, 1988, pp. 311-316
  9. Shirey III, D. B., Demonstration of Efficient Humidity Control Techniques at an Art Museum, ASHRAE Transactions, 99 (1993), pp. 694-703
  10. Yau, Y. H., Theoretical Determination of Effectiveness for Heat Pipe Heat Exchangers Operating in Naturally Ventilated Tropical Buildings, Proceedings, The Institution of Mechanical Engineering, Part A: Journal of Power and Energy, 215 (3) (2001), pp. 389-398
  11. Mathur, G. D., Predicting Yearly Energy Savings Using BIN Weather Data With Heat Pipe Heat Exchangers, Proceedings, The Intersociety Energy Conversion Engineering Conference, Honolulu, USA, 1997, pp.1391-1396
  12. YAU, Y.H., Ahmadzadehtalatapeh, M., The empirical study of a four-row heat pipe heat exchanger to predict the year-round energy recovery in the tropics. Building Serv. Eng. Res. Technol. 32, 4 (2011) PP. 307-327
  13. Yau, Y. H., Application of a Heat Pipe Heat Exchanger to Dehumidification Enhancement in a HVAC System for Tropical Climates - a Base Line Performance Characteristic Study, International Journal of Thermal Science, 46 (2007), pp. 164-171
  14. Yau, Y. H., The Use of a Double Heat Pipe Heat Exchanger System for Reducing Energy Consumption of Treating Ventilation Air in an Operating Theatre - A Full Year Energy Consumption Model Simulation, Energy and Buildings, 40 (2008), pp.917-925
  15. Ahmadzadehtalatapeh, M., Measurements and Modeling of the Horizontal Heat Pipe Heat Exchangers for Saving Energy and Improving Thermal Comfort in Air-Conditioning Systems in the Tropics, Ph.D. thesis, University of Malaya, Malaysia, 2011
  16. ANSI/ASHRAE, Method of Testing Air-to-Air Heat Exchangers, ASHRAE, Atlanta, Standard 84-1991
  17. Kays, W.M., London, A.L., Compact Heat Exchangers Design, McGraw-Hill, New York, 1984
  18. Azad, E, Geoola, F., A Design Procedure for Gravity Assisted Heat Pipe Heat Exchanger, Heat Recovery Systems, 4(2) (1984), pp. 101-111
  19. Noie, S.H., Investigation of Thermal Performance of an-to-air Thermosyphon Heat Exchanger Using ε -NTU Method, Applied Thermal Engineering, 26 (2006), pp. 559-567

© 2024 Society of Thermal Engineers of Serbia. Published by the Vinča Institute of Nuclear Sciences, National Institute of the Republic of Serbia, Belgrade, Serbia. This article is an open access article distributed under the terms and conditions of the Creative Commons Attribution-NonCommercial-NoDerivs 4.0 International licence