TY - JOUR TI - Thermodynamic performance evaluation of an air-air heat pipe heat exchanger AU - Mandapati Mohan Jagadeesh Kumar AU - Chandra Kaushik Subhash AU - Narayan Garg Sat JN - Thermal Science PY - 2014 VL - 18 IS - 4 SP - 1343 EP - 1353 PT - Article AB - In this paper, heat transfer analysis for an air-air heat exchanger was experimentally carried out to find its thermal performance and effectiveness. Air-air heat exchanger equipped with finned heat pipes was considered for the experimentation. Mass flow rate of air was considered in between 0.24 to 0.53 [kg/sec]. The temperature at the condenser side of the heat pipe heat exchanger was kept constant at around 23 [°C] and at the evaporator part it was varied from 88 to 147 [°C]. The performance of heat pipe heat exchanger was evaluated at different mass flow rate of air, in terms of effectiveness and compared with its corresponding value found by theoretical analysis.